The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.
|
Parameter |
Designation |
See |
|
5.10 |
Calling up the parameter level |
|
|
5.11 |
Activating the LIS-SV for the ABULiner |
|
|
5.11 |
Setting the gear ratio |
|
|
5.12 |
Activating double lifting speed |
|
|
5.14 |
Setting the run-on time of the auxiliary fan |
|
|
Danger during setting work! During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things. This means the wire rope hoist cannot be monitored for excess load, among other things. This in turn means the load could fall and kill or injure people! Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes! |
All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.
|
|
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Open the menu of the
LIS-SV. See the documentation “Load indicator system LIS-SV”.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.10.
Press ENTER.
● The 'ABULiner' parameter level is activated.
● Parameter 5.11 is displayed.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.99.
Press ENTER.
● The previous parameter level is reactivated.
● Parameter 5.10 is displayed.
The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.
In the ABULiner mode (a value is set for parameter 5.11):
─ The LIS-SV can monitor the total load for a maximum of two wire rope hoists.
─ Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.
─ A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV cannot be used.
─ Parameter 4.5 (setting for load-controlled switching point) is not available.
In the normal mode (no value is set for parameter 5.11):
─ Operation of the ABULiner Lifting/Lowering unit is not possible.
─ The LIS-SV can monitor the total load for up to three wire rope hoists.
─ Input F3 serves in measuring the load of a third wire rope hoist.
─ A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV can be used.
─ Parameter 4.5 (setting for load-controlled switching point) can be used.
The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.
|
| |
|
Cable speed |
|
Read off the type
designation at the type plate of the wire rope hoist.
Read off the cable
speed.
From this table, select
the gear ratio that matches the cable speed.
|
|
Cable speed | ||||
|
Hoist motor GM |
32 m/min at 50 Hz |
25 m/min at 50 Hz |
20 m/min at 50 Hz |
16 m/min at 50 Hz | |
|
800.4 |
50.01 |
63.49 |
77.77 |
98.16 | |
|
800.5 |
47.03 |
60.04 |
74.66 |
95.03 | |
|
1000.6 |
54.43 |
68.91 |
84.00 |
105.1 | |
|
1000.7 |
54.60 |
68.06 |
81.45 |
104.6 | |
|
2000.3 |
58.22 |
74.23 |
91.19 |
118.4 | |
|
3000.4 |
73.61 |
93.92 |
118.4 |
152.9 | |
|
5000.3 |
85.14 |
109.3 |
132.8 |
169.0 | |
|
5000.4 |
80.20 |
104.9 |
127.7 |
160.6 | |
|
6000.3 |
94.69 |
118.5 |
149.6 |
182.7 | |
|
7000.1 |
118.0 |
148.3 |
182.6 |
232.0 | |
Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.11.
Press ENTER.
● The set value is displayed.
If the value is 0.00, the function is deactivated.
● Hold ENTER pressed.
● CODE is displayed.
Hold ENTER pressed.
|
| |
|
Enter button |
Arrow buttons |
Enter the code 1443.
Press ENTER briefly.
|
| |
|
Enter button |
Arrow buttons |
Set the value from the
table.
If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0. In this case, set the value to zero first.
Press ENTER briefly.
"La Física de Alonso Finn" se caracteriza por su enfoque claro y conciso en la presentación de los conceptos físicos. Los autores han utilizado un lenguaje accesible y han incluido numerosos ejemplos y problemas resueltos para ayudar a los estudiantes a comprender mejor los temas tratados.
"La Física de Alonso Finn" es un tratado de física que cubre los temas fundamentales de la física clásica y moderna. El contenido de la obra se divide en dos volúmenes: fisica de alonso finn volumen 1 y 2 completos pdf
Alonso y Finn son dos reconocidos físicos y educadores que han dedicado su carrera a la enseñanza y la investigación en física. Marcelo Alonso y Jerry Finn son sus nombres completos, y ambos han sido profesores en universidades prestigiosas de todo el mundo. Su experiencia y conocimientos en física les han permitido crear un recurso educativo que ha sido ampliamente adoptado en universidades y escuelas de todo el mundo. "La Física de Alonso Finn" se caracteriza por
"La Física de Alonso Finn" es un recurso educativo completo y valioso para estudiantes y profesores de física. Con su enfoque claro y conciso en la presentación de los conceptos físicos, este libro es ideal para aquellos que buscan profundizar en el conocimiento de la física clásica y moderna. Esperamos que esta información te haya sido útil para acceder a los volúmenes 1 y 2 completos en formato PDF. ¡Buena suerte en tus estudios de física! El contenido de la obra se divide en
La física es una de las ciencias más fascinantes y complejas que existen. Desde la antigüedad, los seres humanos han estado interesados en entender los fenómenos naturales que nos rodean, y la física ha sido fundamental para desentrañar los misterios del universo. En este sentido, los libros de texto de física son herramientas esenciales para estudiantes y profesores que buscan profundizar en el conocimiento de esta disciplina.
The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.14.
Press ENTER.
● The set value is displayed.
|
| |
|
Enter button |
|
Set the value to between 3
and 10 minutes using the arrow buttons.
Press ENTER.